62
Using ProLink
®
Software with Micro Motion
®
Transmitters
View Menu: Status
continued
Operational indicators
"Analog Input Error" and
"Pressure Input Failure"
Analog Input Error applies only to versions 2.0 and higher RFT9739
transmitters. Analog Input Error switches ON when the pressure input to
the RFT9739 is less than 4 mA or greater than 20 mA, and indicates one
of the following conditions:
• Faulty wiring between a pressure transmitter and the RFT9739
• Pressure input requires characterization
Pressure Input Failure applies only to RFT9739 transmitters with
software versions 2.3 and higher. Pressure Input Failure switches ON to
indicate a loss of either the analog input signal, as above, or the HART
signal.
If Analog Input Error or the Pressure Input Failure switches ON:
• Characterize range limits for milliamp input
• Check for faulty wiring to or from pressure transmitter
• Alter fluid process
"Data Loss Possible"
Data Loss Possible switches ON when a power fluctuation occurs during
transmitter configuration, to indicate the last configuration parameters
might not have been saved.
If Data Loss Possible switches ON, open the appropriate configuration
window and check the last parameters that were entered. Re-enter any
parameters that are not correct.
7.4 Operational indicators
Operational indicators switch ON to indicate the following conditions:
• The process is operating outside control limits.
• The transmitter cannot properly calculate settings during a
calibration procedure.
• Inappropriate measurement units or inappropriate limits on output
variables are driving outputs to their limits.
• The transmitter cannot calculate the flow rate.
Table 7-7
summarizes conditions indicated by operational indicators,
and lists appropriate corrective actions.
"Calibration Failure"
Calibration Failure switches ON if the transmitter cannot properly
calculate settings during a calibration procedure. The cause of the
failure depends on the type of calibration that is being performed:
• During auto zero, failure can occur due to mechanical noise from an
external source or due to flow of fluid through the sensor.
• During a two-point density calibration, failure can occur due to use of
a low-density fluid that is too dense, a high-density fluid that is not
sufficiently dense, or mechanical noise from an external source.
For more information about flowmeter calibration, see
Chapter 14
(page
133).
Comentarios a estos manuales